OSHA Establishment Search

Look up any company's OSHA violations and citations by name, state, or city, a free establishment search and citation lookup built directly from public federal enforcement data.

CARTRIDGE ACTUATED DEVICES, INC.

BYRAM TOWNSHIP, NJ

Inspections With Violations1
Total Citations8
Total Penalties$182,067.00
Most Recent CaseNovember 20, 2025

November 20, 2025 · Referral

OSHA case 348606047

29 CFR 1910.119(c)(2) · Serious · $8,276.00

29 CFR 1910.119(c)(2): Employers did not consult with employees and their representatives on the conduct and development of process hazard analyses and on the development of the elements of process safety management in this standard: a) 40 Old Indian Spring Rd, Byram Township NJ 08721 On or about 11/20/2025 and continuing thereafter. The employer failed to consult with employees and their representatives on the development and review of PHAs and other PSM program elements including, but not limited to, management of change, incident investigations, and operating procedures.

Contested May 14, 2026 - not yet finalized.

29 CFR 1910.119(e)(3)(i) · Serious · $8,276.00

29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process; a) 40 Old Indian Rd, Byram Township NJ 07821 On or about 10/24/2025 and continuing thereafter. PHAs, including but not limited to Ignition Element, Electric, MK 17 Mod 0 Assembly CAD Part No. 230224, did not address process hazards including but not limited to, humidity less than 40%, the potential for foreign objects, equipment damage, chemical compatibility, propagation of fire or detonation.

Contested May 14, 2026 - not yet finalized.

29 CFR 1910.119(e)(3)(vi) · Serious · $0.00

29 CFR 1910.119(e)(3)(vi): The process hazard analysis did not address human factors. a) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building and Shipping Building On or about 10/24/2025 and continuing thereafter. PHAs for Ignition Element, Electric, MK 17 Mod 0 Assembly CAD Part No. 2302224 and MK17 Mod 0 Inner Container Assembly CAD Part NO. 2240800 did not address human factors including but not limited to, not seating shorting cap on connector end of assembly of Mk 17 ignition element. The failure to address human factors exposed employees to detonation hazards.

Contested May 14, 2026 - not yet finalized.

29 CFR 1910.119(f)(1)(i)(d) · Serious · $8,276.00

29 CFR 1910.119(f)(1)(i)(D): The employer did not develop and implement written operating procedures that provide clear instructions for emergency shutdown, including the conditions under which emergency shutdown is required, and the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner. a) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Loading Building On or about 10/24/2025 and continuing thereafter. The process operation sheets for assembly of products including Ignition element, Electric, MK 17 Mod 0 Assembly CAD Part No 2302224 and Primer Assembly CAD Part NO 2519610, did not include emergency action steps to cover devices containing explosive materials with aluminum foil.

Contested May 14, 2026 - not yet finalized.

29 CFR 1910.119(j)(2) · Serious · $8,276.00

29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment; a) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building On or about 11/20/2025 and continuing thereafter, the employer did not implement written procedures for inspection or testing of explosion proof electrical wiring. b) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building On or about 11/20/2025 and continuing thereafter, the employer did not implement written procedures for inspection or testing of shield. c) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building On or about 11/20/2025 and continuing thereafter, the employer did not implement written procedures for inspection or testing of arbor presses.

Contested May 14, 2026 - not yet finalized.

29 CFR 1910.119(j)(4)(i) · Serious · $8,276.00

29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment; a) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building On or about 11/20/2025 and continuing thereafter, the employer did not perform inspections on process equipment for 2025 including but not limited to explosion proof electrical wiring. The employer's internal policy requires monthly visual inspections. b) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building On or about 11/20/2025 and continuing thereafter, the employer did not perform inspections on process equipment for 2025 including but not limited to shields. The employer's internal policy requires annual inspections. c) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building On or about 11/20/2025 and continuing thereafter, the employer did not perform inspections on process equipment for 2025 including but not limited to presses. The employer's internal policy requires annual inspections.

Contested May 14, 2026 - not yet finalized.

29 CFR 1910.119(o)(1) · Serious · $8,276.00

29 CFR 1910.119(o)(1): The employer did not certify that they have evaluated compliance with the provisions of this section at least every three years: a) 40 Old Indian Spring Rd, Byram Township NJ 07821 - Load Building On or about 10/24/2025 and continuing thereafter, Compliance audits were not conducted nor documented to evaluate if compliance with procedures and practices are adequate and being followed.

Contested May 14, 2026 - not yet finalized.

29 CFR 1910.119(l)(1) · Willful · $132,411.00

29 CFR 1910.119(l)(1): The employer did not implement procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process: a) 40 Old Indian Spring Rd, Byram Township NJ 07821 - shipping building A change to "Process Operation Sheet for Ignition Element, Electric, MK 17 Mod 0 Assembly CAD part # 2302224" and "Process Operation Sheet for MK 17 MOD 0 Inner Container Assembly CAP Part # 2240800" was made without evaluating impact of change on safety and health through the company's management of change process. On or about 10/24/2025, Mk17 inner container units were moved from production to shipping for packing without safety caps/shunting. Both procedures were red lined, initialed by management, and steps modified to document that shipping would place cap on connector end of assembly instead of production.

Contested May 14, 2026 - not yet finalized.

Potential Matches

Other locations on file under the exact same company name. OSHA News does not combine these with the facility above - a shared name is not proof of a shared company, so click through to judge for yourself whether a listing below is really the same business.

CityStateInspectionsMost Recent
CityFAIRFIELD StateNJ Inspections3 Most RecentNov 20, 2025
CityANDOVER StateNJ Inspections5 Most RecentMar 28, 2014