OSHA Establishment Search

Look up any company's OSHA violations and citations by name, state, or city, a free establishment search and citation lookup built directly from public federal enforcement data.

SHOWPLACE ENTERTAINMENT CENTER

STATEN ISLAND, NY

Inspections With Violations2
Total Citations10
Total Penalties$58,213.00
Most Recent CaseJanuary 30, 2026

January 30, 2026 · Referral

OSHA case 348720087

29 CFR 1910.37(a)(4) · Serious · $3,547.00

29 CFR 1910.37(a)(4): 29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: A) Showtime Entertainment - 141 E. Service Rd., Staten Island, NY 10304 - The employer did not ensure that the emergency lights were intact and fully operational, thereby exposing employees to hazards in the event of an emergency or power failure. Noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

29 CFR 1910.37(b)(6) · Serious · $0.00

29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: A) Showtime Entertainment - 141 E. Service Rd., Staten Island, NY 10304 - The employer did not ensure that the emergency lighting was maintained in working condition, exposing employees to hazards during an emergency. Noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

29 CFR 1910.106(d)(5)(iii) · Serious · $2,837.00

29 CFR 1910.106(d)(5)(iii): 29 CFR 1910.106(d)(5)(iii) Flammable storage was not kept in closed metal containers and were not stored in a storage cabinet: A) Showtime Entertainment - 141 E. Service Rd., Staten Island, NY 10304 - The employer did not ensure that the plastic gasoline containers were stored in an approved cabinet, exposing employees to fire hazards. Noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

29 CFR 1910.303(g)(1)(ii) · Serious · $2,837.00

29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: A) Showtime Entertainment - 141 E. Service Rd., Staten Island, NY 10304 - The employer did not ensure that the electrical room was kept free of cardboard, wood, and other non electrical combustible materials, exposing employees to fire hazards. Noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

29 CFR 1910.303(g)(2)(iii) · Serious · $2,837.00

29 CFR 1910.303(g)(2)(iii): Entrances to rooms and other guarded locations containing energized panels were not marked with conspicuous warning signs forbidding unqualified persons to enter: A) Showtime Entertainment - 141 E. Service Rd., Staten Island, NY 10304 - The employer did not ensure the entrance to electrical rooms were clearly marked warning employees of electrical hazards. Noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

29 CFR 1910.305(a)(2)(i)(b) · Serious · $2,837.00

29 CFR 1910.305(a)(2)(i)(B): Temporary wiring was used for a period exceeding 90 days. A) Showtime Entertainment - 141 E. Service Rd., Staten Island, NY 10304 - The employer did not ensure that the temporary wiring was removed or that permanent wiring was installed. Noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

29 CFR 1910.305(g)(2)(ii) · Serious · $4,965.00

29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: A) Showtime Entertainment - 141 E. Service Rd., Staten Island, NY 10304 - The employer did not ensure that flexible cords were used in continuous lengths without exposed splices, thereby exposing employees to electrical shock hazards. One splice was located approximately one foot from the male end plugged into the wall outlet, and another splice involved connecting a microwave cord to a power strip. Noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

29 CFR 1910.36(d)(1) · Willful · $33,103.00

29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: A) Showplace Entertainment - 141 E. Service Rd., Staten Island NY 10304 - Employees were unable to open the exit door from the inside because the push bar was damaged and would not disengage. The door was also secured from the outside with a dead bolt anchored into the ground, exposing employees to entrapment hazards during an emergency. First cited on April 09, 2025 during inspection 1816669 Incident noted on January 30, 2026

Contested July 31, 2026 - not yet finalized.

April 9, 2025 · Referral

OSHA case 348166695

29 CFR 1910.36(d)(1) · Serious · $3,310.00

29 CFR 1910.36(d)(1):Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a.) Showplace Entertainment Center/141 E Service Road, Staten Island, NY, 10314/Dining room/ The exit door was chained and locked, obstructing safe egress in the event of an emergency. Condition noted on or about 04/09/2025.

Final order entered March 23, 2026.

29 CFR 1910.37(b)(6) · Serious · $1,940.00

29 CFR 1910.37(b)(6):Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: a.)Showplace Entertainment Center/141 E Service Road, Staten Island, NY, 10314/Dining room/In the dining room the exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source preventing safe egress in the event of an emergency. This conditions exposed employees to smoke inhalation. Condition noted on or about 04/09/2025.

Final order entered March 23, 2026.