What Happened
At approximately 4:20 a.m. on February 25, 2025, an employee of Alstom Transportation USA Inc. was working on an AirTrain switch electrical panel in Newark, New Jersey, attempting to replace blown fuses. During the task, he came into contact with energized components and received a 600-volt electric shock. He was fatally electrocuted.
What OSHA Found
OSHA issued seven citations, all classified Serious, for a combined $66,200. The central citation was under 29 CFR 1910.333(a)(1), the requirement that live parts an employee may contact be deenergized before work begins, unless deenergizing would introduce additional or increased hazards, or is infeasible due to equipment design or operational limitations. Related citations covered 29 CFR 1910.332(b)(1) (training for employees who work on or near exposed energized parts), 29 CFR 1910.333(b)(2)(ii)(A) (lockout procedures for deenergizing circuits), and 29 CFR 1910.335(a)(1)(i) (personal protective equipment for electrical work). All seven were contested on September 17, 2025, and no final order has been entered yet.
A Fuse Replacement Should Never Be Done Live
Replacing a blown fuse is routine maintenance, which is exactly why it's dangerous to treat casually. The standards cited here exist for precisely this scenario: before anyone opens a panel to work on it, the circuit is supposed to be deenergized, locked, and verified dead, not worked on live under the assumption that a quick fix doesn't need the full procedure. Our guide to lockout/tagout covers the broader hazardous-energy-control principle this case turned on, even though the specific citations here are electrical-safety standards rather than the mechanical lockout/tagout standard.
Company History
OSHA's own records show this is the only inspection on file for Alstom Transportation USA Inc. under this exact name. We found no outside news coverage specifically describing this incident as of this writing.